Answers are grounded in this paper and cite their sources.
The growing demand for high-power rectification has imposed increasingly strict power quality requirements on modern electrical grids. As prevalent nonlinear front-end devices, multi-pulse rectifiers (MPRs) inject substantial harmonic currents into the AC mains. Targeting the inherent shortcomings of conventional MPRs, this study develops a passive solution—termed the passive auxiliary circuit (PAC)—for harmonic mitigation at the source. The proposed system integrates a 12-pulse main rectifier, based on a delta/wye-connected transformer (DWCT), with the PAC. The PAC contains two interphase reactors (IPRs) and 10 diodes. A detailed operational analysis, grounded in Kirchhoff’s Current Law (KCL), is conducted to determine the circuit’s injection current characteristics across its distinct conduction modes. Furthermore, the IPR turns ratios are evaluated using an analytical input current THD model. The calculated combined apparent power rating of the IPRs is 2.53% of the DC output power, while the auxiliary diode conduction loss is estimated as 1.34ILUon under the constant forward-voltage drop assumption (IL: load current; Uon: diode voltage drop). Simulation and prototype testing support the PAC’s harmonic suppression capability. The measured input current THD is 3.62% at the reported operating point.
No takes yet. Share an insight, caveat, or question.
Gu et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: