Fire alarms announce an emergency but do not tell occupants which way to move, and responders usually arrive without a current count of who is inside. We present SynEvac, a prototype that links a building model, an agent-based simulator, camera-based detection, a digital twin and a hybrid rules-plus-reinforcement-learning decision module. Two design choices set it apart: the decision module sees only what cameras and sensors could observe, never the simulator’s ground truth, and a failed camera lowers confidence in an occupancy estimate instead of resetting it to zero. We compare the simulator with fire-drill measurements published by NIST, where it reaches 93.4% (10-storey) and 91.8% (18-storey) of the reference values, a mean shortfall of 7.4%. We also report a stretcher and fallen-person detector with over 95% validation accuracy, a door-line counter that estimates occupancy of rooms with no camera, and evacuation drills with first-year students. A comparison of our default parameters with the NIST pre-evacuation delays shows that the defaults are optimistic, which we treat as a finding and a task for future calibration.