This analysis compares load shifting in radiant and convective cooling systems, suggesting energy optimization strategies.
As the adoption of renewable energy continues to grow in the building sector, the energy flexibility of air conditioning systems has become a key factor in achieving energy optimization and load shifting. This study systematically compares the performance of radiant and convective cooling systems in both continuous and intermittent operation modes, with a focus on their load shifting capabilities. A dynamic heat transfer model based on the state-space method was established to calculate load transfer indices and node temperature values for both systems under various operating conditions. The results indicate that, under intermittent cooling mode, the radiant cooling system exhibits superior load-shifting capability owing to the high thermal inertia of its radiant terminal and its distinct heat transfer pathway. It enables temporary cooling shutdowns while maintaining indoor thermal comfort for up to one hour, and effectively reshapes the cooling load profile by adjusting the chilled water supply schedule. This study offers a comprehensive comparison between radiant and convective systems, providing practical guidance for improving the adaptability of building cooling systems in future scenarios with high renewable energy penetration.