Simulation reveals increased winding and eddy current losses in dry type hollow reactor due to harmonic pollution.
With the increasing size of the grid, a large number of non-linear equipment applicable, harmonic pollution is becoming more and more serious. Higher demands on the harmonic operation capability of reactor filtering equipment. In this paper, the dry type hollow reactor was taken as a research object, according to the field-circuit coupling principle, the establishment of finite element two-dimensional wire-turn unit electromagnetic simulation calculation model, solved the coil frequency current superimposed on different harmonic current frequency, content curve. Then calculate the winding loss of each layer, carry out the fluid-heat coupling simulation calculation, and get the temperature rise distribution of the reactor. Study shows that:Elevated harmonic content causes an increase in coil current amplitude and excitation of a stronger magnetic field, resulting in an increase in resistance loss and eddy current loss, leading to a rise in reactor temperature. The increase in harmonic frequency marginalizes the reactor coil current density distribution, increases the coil resistance, and leads to an increase in the local magnetic induction strength, resulting in an increase in coil eddy current losses, leading to an increase in reactor temperature.