Numerical simulation reveals optimal pulse durations enhance fire suppression in long, narrow spaces, indicating improved cooling effects.
This study numerically investigated how varying pulse durations of water mist systems influence fire dynamics in long, narrow underground enclosures. A Fire Dynamics Simulator (FDS) model was built to represent a pulse-actuated, fine water mist test rig, and simulations of oil pan fires were performed to quantify the evolution of temperature and radiative heat flux. Results show that an 8 s spray followed by an 8 s pause yields the most effective suppression cycle. When spray and pause durations are equal, periodic momentum exchange resonates with the buoyant plume, intensifying the mixing of gas and enhancing cooling near the fire seat. Compared with continuous discharge, pulsed mist generates stronger buoyancy-driven disturbances and delivers superior performance in terms of local heat’s extraction and extinguishment. This study has, for the first time, determined the optimal pulse cycle (8 s spray/8 s stop) for oil pool fires in narrow and long underground spaces through FDS simulation, and revealed the enhancement effect of the gas disturbance resonance mechanism on fire suppression efficiency.
No takes yet. Share an insight, caveat, or question.
Deng et al. (2025) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: