This research demonstrates a direct optimal control approach for pumps and fans, highlighting energy savings in cooling water systems.
The optimal control of cooling water systems is of great significance for energy saving inchiller plants. Previously optimal control methods optimize the flow rate, temperature or temperature difference setpoints but cannot control pumps and cooling tower fans directly. This study proposes a direct optimal control method for pumps and fans based on derivativecontrol strategyby decoupling water flow rate optimization and airflow rate optimization, which can make the total power of chillers, pumps and fans approach a minimum. Simulations for different conditions were performed for the validation and performance analysis of the optimal control strategy. The optimization algorithms and implementation methods of direct optimal control were developed and validated by experiment. The simulation results indicate that total power approaches a minimum when the derivative of total power with respect to water/air flow rate approaches zero. The power-saving rate of the studied chiller plant is 13.2% at a plant part-load ratio of 20% compared to the constant-speed pump/fan mode. The experimental results show that the direct control method, taking power frequency as a controlled variable, can make variable frequency drives regulate their output frequencies to be equal to the optimized power frequencies of pumps and fansin a timely manner.