This paper presents a model predictive control (MPC) methodology for integrating air-based photovoltaic/thermal (PV/T) systems in school buildings. The methodology is developed based on a case study for an archetype fully electric school building in Québec, Canada. A data‐driven grey‐box model for the classrooms is calibrated with measured data, and a PV/T model is developed. These models are integrated to apply MPC to the school building using the established dynamic tariffs for morning and evening peaks. Three scenarios are investigated and compared: (1) A reference case without a PV or PV/T system, (2) Integration of a PV system and MPC, and (3) Integration of a PV/T system and MPC under a demand response scenario. Results show that using the MPC with PV/T integration can reduce peak demand by up to 100% during high-demand periods for the grid. This methodology is scalable and can be transferable to other institutional buildings.
No takes yet. Share an insight, caveat, or question.
Morovat et al. (2024) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: