Answers are grounded in this paper and cite their sources.
Photovoltaic-thermal (PVT) collectors generate electricity and useful heat, requiring a balance between electrical efficiency and thermal recovery. This study proposes a PVT-Building Digital Twin (PVT-BDT) coupled with Adaptive Pareto Model Predictive Control (AP-MPC) to optimize PVT flow rate, HVAC setpoint, and battery/grid power allocation. A 4C-RC electro-thermal model integrates PVT dynamics, building thermal behaviour, occupant comfort, battery state of charge, and electrical power balance. AP-MPC adapts objective weights using the knee point of a periodically approximated energy–comfort Pareto front. The framework is evaluated through calibrated numerical simulations using experimental PVT parameters and data from the Northern African Industrial Thermal Comfort Dataset (NAITCD). Over six months, AP-MPC reduces net energy consumption by 26% compared with fixed-flow control, increases thermal satisfaction from 76.2% to 90.5%, and improves PVT electrical efficiency by 2–7%. These results demonstrate the potential of adaptive Pareto control for energy-efficient, occupant-centered buildings.
No takes yet. Share an insight, caveat, or question.
Rahmani et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: