This is the authors' abstract. We don't add key points for this paper.
Indirect evaporative cooling (IEC) appears to be a highly promising technology for incorporating and/or substituting traditional air conditioning systems, as it can guarantee good cooling performance with a reduced environmental impact. In this study, a Computational Fluid Dynamics (CFD) model for design and performance prediction of recuperators for IEC systems with dry primary and secondary channels was developed. The model was validated against experimental data for a cross-flow recuperator, obtaining a maximum difference between numerical and experimental results of 4.9% for the secondary air outlet temperature, 5.3% for the primary air outlet temperature, and 8.1% for the dry-bulb effectiveness. After validation, the model was used to find a new plate geometry which guarantees a 12.5-15.9% improvement in the dry-bulb effectiveness, without an excessive increase in the pressure losses along the channels.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Caruana et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: