In the new power distribution system, multi-distributed photovoltaic (PV) systems often exist in the form of either direct parallel connection or indirect interconnection. The virtual synchronous generator (VSG), as a typical grid-forming distributed PV inverter, exhibits different dynamic characteristics with different combinations of control and circuit parameters under grid fault conditions. Current research often focuses on the stability of a single VSG, with few studies addressing the analysis and control of multiple VSG grid-connected systems. Therefore, this paper proposes a method for discriminating VSGs grid-connected system and establishes an equivalent single VSG model for the coherent VSGs grid-connected system, ensuring that the equivalent single VSG system model has a clear physical meaning and can represent the dynamic characteristics of original system. Then, based on the equivalent model, a method for improving the transient performance of the coherent VSGs grid-connected system is proposed. Finally, the correctness of the theoretical analysis is verified through simulation.
No takes yet. Share an insight, caveat, or question.
Liu et al. (2024) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: