This research demonstrates reduced cooling and heating loads in transparent buildings, indicating the effectiveness of geothermal energy utilization.
Transparent building envelopes significantly increase energy demands due to low thermal resistance and solar heat gain, while conventional double-skin facades may lead to overheating and high cooling loads in the summer. This study proposes a novel earth-to-air heat exchanger (EAHE)-assisted ventilated double-skin facade (VDSF) system utilizing low-grade shallow geothermal energy for year-round thermal regulation of transparent building envelopes. A numerical model of this coupled system was developed and validated to estimate the thermal performance of the EAHE-assisted VDSF system in a hot-summer-and-cold-winter climate. Parametric study was conducted to investigate the impact of some key design parameters on thermal performance of the EAHE-assisted VDSF system and further reveal recommended design parameters of this coupled system. The results indicate that the EAHE-VDSF system reduces annual accumulated cooling loads by 20.3% to 76.5% and heating loads by 19.6% to 47.1% in comparison to a conventional triple-glazed, non-ventilated facade. The cavity temperature of the VDSF decreases by 15 °C on average in the summer, effectively addressing the overheating issue in DSFs. The proposed coupled EAHE-VDSF system shows promising energy-saving potential and ensures stability and consistency in the thermal regulation of transparent building envelopes.