Analysis reveals airflow dynamics in deep-buried tunnels, implying improved energy-saving designs for underground buildings.
The goal of this paper is to clarify the heat–moisture coupled regulation mechanism of deep-buried underground air tunnels and to address the research gaps in the heat–moisture coupled transfer between airflow and surrounding rock. This paper established a 560 m deep ventilation shaft with a diameter of 5 m focused on the heat–moisture coupled transfer of “surrounding rock—air tunnel—airflow” to investigate the airflow characteristics; analyze the heat and moisture changes of the tunnel surface and airflow, as well as the energy storage characteristics of the surrounding rock; and compare the induced airflow characteristics across four typical cities in China. The results show the following: there is an “inlet effect” in the deep-buried air tunnel; the wall temperature becomes basically stable after 200 m from the entrance, while a greater depth is required for the stable section of humidity; in summer, the airflow temperature decreases by more than 1 °C and the enthalpy decreases by 3.5 kJ/kg; in addition, the ground temperature in Guangzhou is relatively high, resulting in a limited effect on adjusting the intake airflow. This study aims to provide support for the energy-saving design of fresh air systems in deep-buried underground buildings.