Randomized trial shows significant heat exchange efficiency in underground ventilation tunnels, suggesting optimization for energy use.
Amidst global carbon neutrality goals, China’s building energy consumption gains prominence, with heating and cooling exceeding 50% of the total. Underground structures leverage inherent geological thermal inertia to significantly reduce ventilation energy demands. This study employs combined field measurements and numerical simulations to investigate heat exchange mechanisms and performance in underground hydropower station air intake tunnels. Four representative tunnels (Sichuan, Fujian, Hebei, Yunnan) served as case studies, monitoring air temperature, humidity, velocity, and wall temperature. Field-monitored parameters informed a computational fluid dynamics (CFD) model, enabling quantitative analysis of rock thermal conductivity, inlet air velocity, and wall temperature effect on heat exchange efficiency. Research shows that: (1) significant seasonal adaptive characteristics exist, achieving peak cooling efficiency (69.04%, summer) and heating efficiency (78.86%, winter); (2) rock thermal conductivity is the primary efficiency determinant—quartzite tunnels exhibited 11.8% higher average efficiency than tuff tunnels; and (3) inlet air velocity negatively correlates with efficiency, exceeding 90% at 0.1 m/s but declining to 69% at 1.5 m/s. This work provides a theoretical basis for optimizing energy-efficient ventilation in underground engineering and validates the pivotal role of rock thermal inertia in reducing operational building energy consumption.
No takes yet. Share an insight, caveat, or question.
Ren et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: