Answers are grounded in this paper and cite their sources.
Photoacoustic spectroscopy enables real-time detection limit of 18.6 ppb dissolved acetylene in transformer oil, suggesting effective monitoring for high-voltage power equipment.
In this work, we report a compact and highly sensitive photoacoustic spectroscopy (PAS) system based on a cone–sphere coupled photoacoustic cell (CSC-PAC) for real-time detection of trace acetylene (C2H2) dissolved in transformer oil. The sensing module integrates a conical resonator with a spherical cavity, forming a hybrid structure that effectively enhances photoacoustic confinement and energy coupling efficiency. Finite element thermo-viscoelastic simulations were employed to optimize the cavity geometry and resonance conditions for maximum signal generation. Experimental results demonstrate a strong linear correlation between the photoacoustic signal and C2H2 concentration (R2 > 0.999), with a sensitivity of 2.45 µV·ppm−1. Allan deviation confirms a detection limit of 18.6 ppb is achieved at a 400 s averaging time, confirming excellent system stability. The miniaturized light-acoustic spectroscopy sensor, with a total volume of 7.5 mL and a rapid response time of 25.5 s, provides a high-performance and field-deployable platform for on-site monitoring of high-voltage power equipment and other industrial applications.
No takes yet. Share an insight, caveat, or question.
Yang et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: