A novel sensor reveals low-cost detection of carbon monoxide in transformer oil, indicating improved safety and sensitivity.
In this paper, we proposed a quartz‐enhanced photoacoustic spectroscopy (QEPAS) sensor system for detecting dissolved carbon monoxide (CO) in transformer oil. The sensor system was designed to be highly sensitive, compact, and cost‐effective. An on‐beam configured acoustic micro‐resonator (AmR) coupled with a quartz tuning fork functions as an acoustic transducer to enhance photoacoustic signals. This sensor system achieved a minimum detection limit (MDL) of 0.37 ppm for CO based on the absorption line with a wavelength of 2333.72 nm. This value is three orders of magnitude lower than the safety threshold specified in relevant standards for dissolved gas detection in transformer oil. The proposed method offered high sensitivity, low cost, a compact form factor, and ease of integration, offering a novel technical solution for dissolved gas detection in transformer oil.
No takes yet. Share an insight, caveat, or question.
Luo et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: