Answers are grounded in this paper and cite their sources.
Legacy On-Load Tap Changer (OLTC) systems in distribution substations are often vulnerable to phase reversal errors, voltage fluctuations, and mechanical degradation, particularly in resource-constrained environments. These challenges degrade voltage regulation accuracy and accelerate wear in OLTC components due to excessive or incorrect tap operations. This paper presents a cost-effective retrofit control strategy designed to enhance the reliability and performance of mechanical OLTC systems. The proposed solution integrates real-time phase sequence detection, adaptive tap control logic using hysteresis thresholds, and automatic motor direction correction to prevent erroneous tap movements. A comprehensive MATLAB-based simulation validates the methodology under various operational scenarios, including reverse power flow, phase reversal, and voltage sags/swells. The strategy is also experimentally deployed in a live 11 kV/433 V university distribution substation. It covers diverse loads such as administrative cum academic blocks, laboratories, guest house cum hostels, and HVAC systems. In this university campus scenario, it demonstrates a 66 % reduction in tap changes, enhanced Mean Time Between Failures (MTBF), and 80 % fewer manual interventions. The outcomes confirm that the proposed retrofit enhances voltage stability, operational efficiency, and system longevity, making it a scalable and economically viable solution for ageing power distribution infrastructure.
No takes yet. Share an insight, caveat, or question.
Hemparuva et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: