Examines electrical measures after replacing metal halide lamps with LEDs, indicating significant implications for public lighting renovations.
The recent trend for large-scale replacement of luminaires using discharge light sources with LED luminaires without any significant adjustments to the electrical installation has generated controversy. This study examines the main electrical measures in a large outdoor lighting installation before and after the replacement of a large number of metal halide floodlights with LED luminaires. The electrical parameters of both technologies are discussed in detail and compared, with special attention given to the odd-numbered harmonics of voltage and current, the generated wave deformation, currents in the neutral conductor, the wattless reactive volt amps and the peak inrush currents. At cold start-up, the LED luminaires generate large power-on currents, much larger than those generated by the metal halide lamps, despite requiring 36% less real installed power. This is a basic problem to be solved when planning a public lighting renovation with LED luminaires as the rest of electrical parameters are reduced. To address this problem, it is proposed to energise the luminaires using magneto-thermal protection circuits with slow trip curves that will tolerate the large short-term inrush currents.