Answers are grounded in this paper and cite their sources.
Experimental study demonstrates reduced third-order harmonic currents and cable losses in low-voltage lighting circuits, highlighting mitigation through lamp diversity and autotransformers.
An experimental investigation of diversity factors of CFL (compact fluorescent lamps) in combination with LED (light emitting diode) lamps is presented in this paper. Attention was paid to the reduction of low–order harmonic currents, especially the third one; which is mainly responsible for the strong increase in power losses in the neutral conductor of low–voltage installations. The harmonic currents drawn by several LED and CFL lamps with nominal powers < 25 W were first measured to investigate the electrical characteristics of individual lamps. In addition, a series of experiments was conducted in which LED lamps were powered between lines through small autotransformers thus avoiding the use of the neutral conductor. The results showed in both cases a sensible reduction of the harmonic current of third order and therefore a marked reduction of the power losses associated with them.
No takes yet. Share an insight, caveat, or question.
Milardovich et al. (2017) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: