This study proposes a systematic approach for implementing discrete-time Linear Active Disturbance Rejection Control in the closed-loop regulation of power converters. The continuous-time Linear Extended State Observer was discretized using the zero-order hold method to obtain a current estimator-based Linear Extended State Observer that is suitable for real-time implementation. The design considerations for discrete-time Linear Active Disturbance Rejection Control, including the selection of observer and controller parameters and the sampling period, are addressed. For performance comparison, a PI controller was designed and implemented in discrete time. The control schemes were evaluated via MATLAB/Simulink (2025b) simulations and real-time closed-loop experiments on a microcontroller to assess the transient response, disturbance rejection capability, and steady-state accuracy of the buck converter. The simulation and experimental results demonstrate that the discrete-time Linear Active Disturbance Rejection Control incorporating a current-estimator-based Linear Extended State Observer significantly outperforms the PI controller in terms of transient response and disturbance rejection capability. From this perspective, this study provides a meaningful contribution to the limited literature on linear extended state observer-based discrete-time Active Disturbance Rejection Control methods.