Answers are grounded in this paper and cite their sources.
An adaptive system for protecting a distribution network should determine and implement relay settings that are most appropriate for the prevailing state of the power system. This paper presents a technique for determining coordinated relay settings. The technique uses the Simplex two-phase method; Phase I determines whether the constraints selected for illustrating the conditionality between primary and back up relays are feasible, and Phase II finds the optimal relay settings. A looped distribution system, protected by directional overcurrent relays, was used for testing the technique. The tests were conducted in a laboratory environment; some results from those tests are reported in the paper.
No takes yet. Share an insight, caveat, or question.
Chattopadhyay et al. (1996) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: