Answers are grounded in this paper and cite their sources.
Evaluates cooling performance enhancements in transformer radiators, highlighting design implications.
• Validated conjugate CFD for ODAN radiator bank (1.8% Q error, 0.1% Tout). • Radiation adds about 14% of heat rejection and improves natural convection. • Cooling capacity drops 25 to 35% per 10°C rise in ambient temperature (20 to 50°C). • Straight chimneys raise cooling up to 16.2% at 5 m via buoyancy draft. • Convergent, deflector and unified designs reduce Q; radiator upgrades cost less. Power transformers are key grid assets whose reliability depends on effective heat rejection. Oil Directed Air Natural (ODAN) radiator banks rely on buoyancy driven airflow and are therefore sensitive to hot ambient conditions. This study validates a conjugate computational fluid dynamics (CFD) model of an industrial ODAN radiator bank against manufacturer tests, then uses it to quantify hot ambient performance losses and to evaluate passive chimney extensions. The model predicts total heat dissipation within 1.8% and a weighted oil outlet temperature within 0.1% of measurements and shows that surface to surface radiation contributes about 14% of the total heat rejection under natural convection. Parametric simulations over ambient temperatures from 20 to 50°C and oil inlet temperatures from 54.8 to 105°C show a strong monotonic reduction in cooling capacity with ambient temperature, with losses of about 25 - 35% per 10°C increase at fixed oil inlet conditions. Straight chimneys increase buoyancy draft and raise cooling capacity approximately linearly with height, reaching a 16.2% gain for a 5 m extension. Convergent, deflector equipped, and unified chimney variants reduce performance because added minor losses and recirculation weaken plume coherence. A first order cost screening indicates that conventional radiator geometry upgrades provide greater thermal gains per unit cost than stainless steel chimneys under the assessed assumptions. These results provide design guidance for improving the robustness of ODAN passive cooling under hot ambient conditions.
No takes yet. Share an insight, caveat, or question.
Sorte et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: