Answers are grounded in this paper and cite their sources.
A new voltage-dependent methodology for shunt-capacitor compensation of primary distribution feeders is presented. A generalized computer- based procedure is described for optimally sizing and placing any specified number of fixed shunt capacitors while accounting for voltage variation along the feeder. The procedure is applied to a physically-existing feeder with known P, Q loads to yield results for capacity release exactly comparable to those from an optimal power flow. The superiority of the new methodology over existing methods is demonstrated.
No takes yet. Share an insight, caveat, or question.
Grainger et al. (1982) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: