This is the authors' abstract. We don't add key points for this paper.
Due to the integration of renewable-based distributed generation units (DGUs), energy storage systems (ESSs), and electric car charging stations, more and more power electronic converters are connected to the grid. In grids with a high penetration rate of these converters, high-current oscillation may happen, which can damage the grid equipment or cause a blackout. Passivity theory is used to design converter controllers in order to alleviate this problem in a decentralized fashion. However, the proposed methods are mostly model-based and are sensitive to parametric uncertainty. This article presents a robust data-driven frequency-domain grid-connected converter controller design with the possibility of defining robust passivity conditions on a performance channel. In addition to robust passivity, the controller design guarantees tracking and disturbance rejection performance. All performance and passivity conditions are written as constraints on closed-loop sensitivity functions and then changed to frequency-domain inequalities and convexified around an initial stabilizing controller. The controller design problem is converted to a convex optimization problem that can be solved efficiently using available solvers. The proposed method is validated by a power-hardware-in-the-loop (PHIL) experiment, including a switching inverter, real-time simulator, and <tex-math notation="LaTeX">$LCL$ </tex-math> filter.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Madani et al. (2023) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: