An offline ambient temperature corrected transmission line (T/L) dynamic thermal rating system is being developed at PG&E (Pacific Gas and Electric) to provide T/L ratings 1 to 24 hours ahead based on hourly ambient temperature measurements at a given location. A low minimum 2 ft/s constant wind speed is assumed at all times. Solar radiation is calculated by an analytical solar model assuming clear sky conditions. The IEEE/ANSI ampacity standard is used to calculate T/L ampacity. In the ambient corrected DTR (dynamic thermal rating) system, a stochastic/deterministic model forecasts ambient temperatures. The forecasts and the standard deviations of forecast errors are updated every hour. T/L ratings were evaluated at PG&E locations and gains of up to 34% over the static line ratings were possible at both locations by the proposed DTR system. The benefits and the risk of the ambient corrected DTR system have been quantified.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>