Answers are grounded in this paper and cite their sources.
The Energy Management System (EMS) is a strong need for achieving cost-effective, reliable, and pollution-free operation of microgrids operating in isolated areas. Commonly, the EMS approaches use optimization and rolling-horizon predictions. However, the inclusion of very short-term predictions increases the complexity of the optimization, compromising its ability and reliability to operate online. In response to this problem, this paper proposes a rule-based EMS (RB-EMS) which uses neither optimization nor prediction horizons. Instead, the RB-EMS evaluates historical data, and very short-term predictions to calculate the setpoints of distributed energy resources, and schedulable loads in a cost-effective, reliable, and sustainable manner. As a form of self-regulation, the RB-EMS introduces the Reliability Index to calculate the maximum state of charge of the energy storage system. Given the speed imposed by the very short-term predictions, the RB-EMS also introduces a start-up manager for diesel units that present a dead time in their enlistment. The isolated ESUSCON-HUATACONDO microgrid was used as a testbed for performance validation. The work shows a first scenario comparing the RB-EMS against a rolling horizon EMS based on MILP optimization. A second scenario shows the energy management performance with 1 minute predictions. The better results obtained, and the computational simplicity of the RB-EMS allows propose it to achieve faster and more reliable energy management in other isolated microgrids.
No takes yet. Share an insight, caveat, or question.
López‐Santiago et al. (2021) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: