It is shown in this paper that voltage sags experienced by three-phase loads, such as adjustable-speed drives, can be classified into four types. Each sag can further be characterized by a magnitude and a phase-angle jump. Relations between fault type, sag type and load connection are presented. The transfer of sags through transformers is discussed. The magnitude and phase-angle jump of sags are directly related to the voltage in the faulted phase, or between the faulted phases, at the point-of-common coupling between the load and the fault.