Three-phase grid-connected inverter with the LCL filter is commonly controlled in synchronous frame in order to independently control active power and reactive power. And proportional-integral controller is usually adopted in synchronous frame to achieve zero steady error of inverter fundamental current. However, d-q axes cross-coupling issue may deteriorate the dynamic and steady-state performance. Moreover, the weak damping characteristic of the LCL filter will lead to resonance issue. Both issues are analyzed by the established complex-vector model of the inverter in this article. A novel multicell network control structure is proposed to address both coupling and resonance problems. To design all parameters of the multicell network controller, a multiple parameter design method is proposed. Moreover, this design method can adapt to weak grid well. Based on the proposed control structure and design method, d-q axes cross-coupling issue can be addressed thoroughly, and the damping performance is also improved obviously. Besides, the excellent steady-state and dynamic performances are realized simultaneously. Finally, the superior performances of the proposed control are verified by simulation and experimental results.
No takes yet. Share an insight, caveat, or question.
Li et al. (2020) studied this question.