Model-based control design reduces DC-link harmonics in reversible solid oxide electrolyser plants, suggesting improved stability and power quality.
This paper presents a model-based, analytical control design for the multiple bidirectional DC–DC converters interfacing individual stacks in a full-scale, cyclically operated reversible solid oxide electrolyser plant to mitigate DC-link harmonics. The distributed synchronous cycling of the rSOE stacks excites low-frequency harmonics and induces DC-link oscillations that degrade stability and power quality. To analyze and mitigate these effects, we develop a control-oriented, linearized small-signal model of the rectification stage, DC distribution network, and converter–stack subsystems, assembled into a plant-level state-space representation. This model enables analytical PI control design for closed-loop pole placements, where there is an inherent trade-off in the control design between dampening DC-link oscillations and maintaining fast reference tracking performance. Simulation results validate the model’s fidelity and demonstrate that the proposed control design strategy effectively reduces DC-link oscillations while preserving acceptable tracking dynamics. A baseline study shows that traditional control methods fail to capture critical plant dynamics, potentially leading to instability.
No takes yet. Share an insight, caveat, or question.
Jessen et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: