A field-oriented technique is described by which partial discharge sites can be located within operating transformers. The method is based on the enhancement of the acoustic emission signals emanating from P.D. sources. No special electrical excitation is required and the calculations involved require only simple arithmetic. The complex nature of the speed of sound in transformer oil is discussed and the need for further work identified