Because of lower voltage levels and smaller power ratings, the R/X ratio of commutation impedance in industrial AC/DC distribution systems is usually higher than that in HVDC transmission systems. Considerable discrepancies may therefore occur in industrial AC/DC power flow results, especially the reactive power consumption of converters, if the commutation resistances of the converters are neglected. To describe the effects of commutation impedance on converter operations and to precisely relate the fundamental line current and DC output current of the converter, a detailed model of the bridge converter with commutation impedance for use of Newton-Raphson power flow studies in industrial AC/DC power systems is derived in this paper. A coal mine power system and a DC electrified transit railway system with regenerative braking function, a part of Taipei Rapid Transit Systems under planning, have been analyzed to show the improved accuracy and good convergence characteristics of the developed Newton-Raphson power flow formulation with the proposed converter model.>
No takes yet. Share an insight, caveat, or question.
Tzeng et al. (1995) studied this question.