Fault tolerance is gaining growing interest to increase the reliability and availability of distributed energy sources. Current sensor fault detection, isolation, and reconfiguration are presented for a voltage-oriented controlled doubly fed induction generator, which is mainly used in wind turbines. The focus of this analysis is on the isolation of the faulty sensor and the actual reconfiguration. During a short period of open-loop operation, the fault is isolated by looking at residuals calculated from observed and measured signals. Then, replacement signals from observers are used to reconfigure the drive and reenter closed-loop control. Laboratory measurement results are included to prove that the proposed concept leads to good results.