Answers are grounded in this paper and cite their sources.
This paper presents the implementation of a single-phase solid-state transformer (SST) for the interface between a 13.2 kV medium voltage alternative current (MVAC) network and a 750 V bipolar DC distribution. The SST has ten cascaded subunits in consideration of the device rating and modulation index (MI). Each subunit consists of an AC/DC stage and a DC/DC stage with a high frequency isolated transformer (HFIT). The AC/DC stage consists of cascaded H-bridges (CHBs) to cope with the MVAC. The DC/DC stage employs a triple active bridge (TAB) converter for bipolar DC distribution. Topology analysis and controller design for this specific structure are discussed. In addition, the insulation of HFIT used in DC/DC converters is also discussed. A simple balancing controller at the AC/DC stage and a current sharing controller at the DC/DC stage are used to prevent DC-link voltage unbalance caused by the cascaded structure. The discussions are validated using a 150 kW single-phase 21-level SST prototype at the laboratory level.
No takes yet. Share an insight, caveat, or question.
Yun et al. (2018) studied this question.