Answers are grounded in this paper and cite their sources.
This paper presents a damped oscillating voltage generator with a novel topology. In the proposed system, a sinusoidal voltage shape, rather than a cosinoidal shape, is used to detect the partial discharge (PD) of medium-voltage distribution power cables. Since this scheme uses a lithium battery instead of a high-voltage dc source, a mains power supply is unnecessary. The energy-storage device is used as an inductor rather than a capacitive test object, thus ensuring that the energizing process is successful even during the test of a deeply deteriorated specimen. This paper describes the working principle and the assembly and implementation of a laboratory prototype for the PD detection of a 200-m cable circuit. The experimental results prove the feasibility of the scheme.
No takes yet. Share an insight, caveat, or question.
Hóu et al. (2015) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: