The Lorentz formula is applied to the calculation of the electromagnetic forces acting on the stator end windings of a turbogenerator within the first several periods after it is suddenly short-circuited, based on the magnetic field computed by the transient quasi-3D method (TQM). The principle of TQM and its essence-processing of winding currents-have been discussed. In the example, the forces acting on the stator end windings of a 35 MW turbogenerator have been computed, when it is under no-load three-phase, no-load line-to-line and no-load line-to-neutral sudden short circuit conditions. Some useful results are obtained.