Among various types of ground heat exchangers (GHEXs or GHEs), a coaxial-type GHEX exhibits outstanding thermal performance owing to the geometric characteristics of the concentric tube-in-tube configuration. In this study, the unique configuration of the coaxial-type GHEX was investigated through parametric studies , which provided the energy efficient configuration. A computational fluid dynamics (CFD) model was developed and verified by using the field test results for the coaxial-type GHEX constructed in a test bed. Then, the parametric studies were conducted using the developed CFD model for various influential factors (i.e., flow rate of a circulating fluid, hydraulic diameter , and thermal conductivities of inner pipe and bentonite grout), which were selected considering the tube-in-tube configuration. The thermal performance of the coaxial-type GHEX increased with an increase in the flow rate of a circulating fluid and the thermal conductivity of bentonite grout. In addition, the inner pipes of the coaxial-type GHEX should be composed of materials with a thermal conductivity lower than 0.025 W/(m⋅K) to relieve thermal interference between the outer and inner pipes. Notably, it was concluded that the coaxial-type GHEX should be designed to secure the sufficient heat exchangeable area and retention capacity of the circulating fluid.
No takes yet. Share an insight, caveat, or question.
Lee et al. (2022) studied this question.
Synapse has enriched one closely related paper. Consider it for comparative context: