A scalable event identification system for power quality events is proposed. Unlike ANN-based approaches where the system is not scalable and not "debug-able" without retraining, the proposed approach is particularly advantageous compared to those of ANN's since it is scalable, debug-able and easily modified. This approach is adopted from artificial intelligence's rule-based approach and attempts to mimic power engineers thought process in identifying PQ events. This paper describes prerequisites in constructing such a scalable system. Examples of rules to identify power quality event are also presented. The prototype of the system is built and tested using 770 field-measured voltage waveforms which covers ten types of PQ events. The accuracy rate is nearly 95% with less than 6% of rejection rate. Potential applications of the proposed system in PQ community are also described.
No takes yet. Share an insight, caveat, or question.
Santoso et al. (2000) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: