Answers are grounded in this paper and cite their sources.
The deterioration concrete structures due to aggressive environmental agents and water action poses a significant threat to the durability and operational safety of water supply systems. This study aims to analyze and diagnose the pathological manifestations of an elevated reinforced concrete water tank located in Palmeira dos Índios, Alagoas. The methodology employed a multi-tool approach, including sensory inspections, the development of a detailed Damage Map using CAD, carbonation testing with phenolphthalein, and chloride penetration tests, alongside the calculation of the Damage Gravity Degree (G) and the Global Structure Deterioration Degree (Dg). The results identified several critical pathologies, most notably carbonation-induced corrosion, cracks caused by thermal shrinkage and hydrostatic pressure, and moisture stains related to infiltration. These findings culminated in a ‘Poor’ structural condition rating, underscoring an urgent need for corrective maintenance and specialized recovery interventions to prevent structural failure and ensure the continuity of potable water distribution to the local population.
No takes yet. Share an insight, caveat, or question.
Oliveira et al. (2026) studied this question.