Answers are grounded in this paper and cite their sources.
This paper presents anti-pollution design criteria for line and station insulators based on investigation of performance of various insulators under artificial pollution tests. Field pollution areas were classified into six classes; AA, A, B, C, D and E according to pollution degree. Recommended leakage distance for disc insulators per 1 kV of nominal line-to- line voltage are 0.75", 0.9", 1.0" and 1.1 " for A, B, C and D areas respectively. Considerable increase in leakage distance is necessary for cylindrical post insulators and porcelain shells with increase in average diameter.
No takes yet. Share an insight, caveat, or question.
Kimoto et al. (1972) studied this question.