The applicability of the ANSI loading guide for power transformers is limited to ambient temperatures above 0 degrees C because the thermal model does not account for variations in the oil viscosity and winding resistance. A practical calculation method based on the bottom-oil temperature and the surface temperature at the top of the cooling duct has been developed. Results indicate that the proposed thermal model could provide a sound basis for calculating the overload capacity for ambient temperatures below 0 degrees C or for severe overloads of short duration.>
No takes yet. Share an insight, caveat, or question.
Aubin et al. (1992) studied this question.