In this paper, an adaptive method for tuning a proportional-resonance controller for synchronization of the grid-connected inverters is presented. In the proposed approach, the grid frequency is obtained by minimizing the error signal using a frequency-locked loop mechanism that consists of a resonant adaptive filter and a perturbation-based extremum seeking algorithm. Simulations and experimental studies are presented to demonstrate performance of the proposed controller in face of the frequency variations of an emulated grid voltage waveform. The results are compared with conventional nonadaptive methods, which indicate that performance characteristics for voltage/frequency tracking and power factor can be achieved based on the IEEE 1547 standard.
No takes yet. Share an insight, caveat, or question.
Seifi et al. (2018) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: