A source voltage sensorless estimation scheme is proposed for a pulsewidth-modulation (PWM) rectifier in unbalanced circumstances. The negative sequence is accompanied by the unbalance among phases, and acts as an ac disturbance to a normal-mode estimator and controller. Hence, without considering voltage unbalance, a PWM rectifier yields a voltage ripple in the dc-link voltage and large reactive currents. With the proposed sensorless scheme, both positive and negative components are estimated separately by using a full- (or reduced-) order estimator. The feasibility of the proposed sensorless scheme is confirmed through computer simulation and experiment.
No takes yet. Share an insight, caveat, or question.
Song et al. (2003) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: