Current limit control can protect converters from overcurrent damage during fault transient but may simultaneously deteriorate the transient synchronization stability. This paper focuses on the transient stability analysis and enhancement of the grid-forming renewable energy system integrated via a voltage source converter based high-voltage direct current (VSC-HVDC) link, considering current limit. First, the switched dynamic model of the studied system under current limit is developed. It is found that switching between voltage control mode and current restricted control mode occurs when the power angle difference between the renewable energy inverter and the VSC-HVDC rectifier reaches a specific value. Accordingly, the transient stability mechanism of the studied system is analyzed using the system's power-angle curve, and the transient stability criterion is derived from the segmented equal-area criterion. On this basis, an optimal tuning strategy for the saturation current angle is further proposed to enhance the transient stability of the system. Simulation results verify the accuracy of the derived stability criterion and the effectiveness of the proposed parameter-tuning strategy.