Characteristics of a vacuum arc under an axial magnetic field have been investigated. The confinement effect of the arc between the electrodes is clearly demonstrated. By this effect, it was found that the arc is significantly stabilised, and consequently the interrupting ability of the arc increases. A demonstration of the current interruption up to 200 kA r.m.s. is shown and the design philosophy of the interruption is discussed.
No takes yet. Share an insight, caveat, or question.
Yanabu et al. (1979) studied this question.