Answers are grounded in this paper and cite their sources.
The practicality of using vacuum interrupters for switchgear applications has been demonstrated by the successful development of a number of prototype devices. Interrupting tests have been made at currents up to 43,000 amp (amperes) at 15.5 kv and recovery rates up to 6,000 volts/μsec (per microsecoind). This has been achieved by resolvinlg many difficult technical problems, so that the vacuum interrupter now closelyr approaches the functional specification of an ideal interrupting device.
No takes yet. Share an insight, caveat, or question.
Lee et al. (1962) studied this question.