This paper presents a new method for locating faults on three-terminal power lines. Estimation of a distance to fault and indication of a faulted section is performed using three-phase current from all three terminals and additionally three-phase voltage from the terminal at which a fault locator is installed. Such a set of synchronized measurements has been taken into consideration with the aim of developing a fault-location algorithm for applications with current differential relays of three-terminal lines. The delivered fault-location algorithm consists of three subroutines designated for locating faults within particular line sections and a procedure for indicating the faulted line section. Testing and evaluation of the algorithm has been performed with fault data obtained from versatile Alternate Transients Program-Electromagnetic Transients Program simulations. The sample results of the evaluation are reported and discussed.