This paper covers the development of a 5,000,000-kva compressed air circuit breaker rated 115,000 and 138,000 volts with 1,200-ampere continuous current-carrying capacity. The breaker is of the conventional dead-tank outdoor construction with one tank per phase. It has two condenser-type bushings extending through the top of each tank for connecting to the customer's bus structure and for mounting of current transformers and potential devices. Preliminary dielectric tests were made with a variety of electrode shapes over a wide pressure range in a grounded-steel pressure vessel. Verification tests were made with 88 kv and 66 kv to ground across two interrupters in series and with 44 kv and 22 kv to ground across a single interrupter. Additional testing was done to establish the thermal capacity and line-dropping ability of the breaker, and to check the voltage distribution across the series interrupters.