Answers are grounded in this paper and cite their sources.
This paper presents and verifies a new mathematical model to explain the dynamic behavior of characteristic gases in the oil-cellulose insulation of high voltage devices like power transformers. The model is based on the diffusion process. Parameters of the model are already quantified from experiments and presented in previous publications. The mathematical model and assumptions are presented here. The model solution is obtained analytically and gas concentration change inside the paper insulation as a function of time is simulated. The results are converted to the concentration change in the oil using the principle of conservation of mass and validated with experimental measurements. The presented model can be used to reduce the error of dissolved gas analysis due to the migration of characteristic gases inside a healthy power transformer.
No takes yet. Share an insight, caveat, or question.
Shahsiah et al. (2007) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: