The static state of an electric power system is defined as the vector of the voltage magnitudes and angles at all network buses. The static-state estimator is a data-processing algorithm for converting redundant meter readings and other available information into an estimate of the static-state vector. Discussions center on an approximate mathematical model (related to the dc load-flow model). This model yields noniterative-state estimation equations, simplified prediction of effects of network and generation-load pattern changes on network flow, and simplified detection and identification of modeling errors. Results of some initial computer studies on the real power-voltage angle portion of the approximate model are discussed.