Dual active bridge (DAB) is a topology that is receiving more and more attention as a potential solution to interface dc grids of different voltage levels. From a system level, the implications of DABs on the stability of complex power systems are addressed in this paper. Dynamics modeling and stability assessment for a DAB implementation aimed to interface low-voltage energy resources with medium-voltage dc (MVdc) collection and distribution grids are presented. The DAB admittance is analytically derived and assessed in order to describe its dynamics and anticipate its behavior when integrated in a complex MVdc grid. The model considers the low-frequency range, mostly dominated by the controller action, and the high-frequency range, described by a nonlinear operation. The theoretical analysis is verified by hardware-in-the-loop emulation, with the controller running on a digital signal processor. The proposed implementation is proved to achieve passivity in the whole spectrum, which undoubtedly is a desired feature for massive power electronics integration in the future MVdc grids.
No takes yet. Share an insight, caveat, or question.
Freijedo et al. (2018) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: