Answers are grounded in this paper and cite their sources.
Faults in inverter-based islanded microgrids can be a formidable protection challenge due to (i) low fault current magnitudes, (ii) compromised fault current phase angles, and (iii) bidirectional flow of fault currents. This paper proposes a protection scheme that disregards the fault signals altogether. Instead, it relies on decoupled synthesized signals introduced only during fault conditions. This scheme is achieved by exploiting the existing inverter-based distributed generation (IBDG) controllers to inject synthetic harmonic voltages and currents. These synthetic signals are measured locally by digital relays in the microgrid to develop a novel synthetic harmonic distance relay (SHDR). Apart from the utilization of high-order harmonic signals that enhance SHDR reactance reach, further reach improvement is achieved via the introduction of line reactance magnifiers (LRMs). Transient studies in PSCAD/EMTDC verify the performance of the proposed scheme under various faults, contingencies, and different microgrid configurations.
No takes yet. Share an insight, caveat, or question.
Saleh et al. (2021) studied this question.